首页> 外文会议>International Conference on Power Electronics-ECCE Asia >Imbalanced fault detection using real time symmetrical coordinate calculation with memorized data
【24h】

Imbalanced fault detection using real time symmetrical coordinate calculation with memorized data

机译:利用存储数据的实时对称坐标计算实现不平衡故障检测

获取原文

摘要

This paper proposes a real time symmetrical coordinate transformation applied for detection of imbalanced fault in utility power system. The power conditioner of the photovoltaic system in Japan is required to remain connected when the utility power system fault occurs under certain condition. The most popular fault is 1 line-to-ground fault. The next is 2 line-short fault. Both cause the imbalance voltages and currents in 3-phase power system. To optimize the output from the power conditioner of the photovoltaic system, the detection of the imbalanced condition is important factor. In this paper, new development of the signal processing method by using the complex number algebra in real time system is shown. The fast detection of the imbalanced condition is verified by the computer simulations.
机译:提出了一种实时对称坐标变换技术,用于电力系统不平衡故障的检测。当在一定条件下发生市电故障时,日本光伏系统的电源调节器必须保持连接状态。最受欢迎的故障是1条接地故障。接下来是2线短路故障。两者都会导致三相电力系统中的电压和电流不平衡。为了优化光伏系统功率调节器的输出,不平衡条件的检测是重要的因素。本文展示了在实时系统中利用复数代数处理信号的新方法。通过计算机仿真验证了对不平衡状态的快速检测。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号