首页> 外文会议>International Conference on Electrical Sciences and Technologies in Maghreb >Behaviour of Cross-linked Polyethylene Used as High Voltage Power Cables Insulation Due to Environmental Constraints
【24h】

Behaviour of Cross-linked Polyethylene Used as High Voltage Power Cables Insulation Due to Environmental Constraints

机译:由于环境限制,用作高压电力电缆绝缘的交联聚乙烯的行为

获取原文

摘要

Crosslinked polyethylene (XLPE) power cables are increasingly used in power distribution system for their excellent mechanical and electrical performance. Nevertheless, it is well known that degradation under environmental conditions is the major problem in the use of this material as insulation in cables. In this paper, artificial weathering tests on XLPE used as high voltage power cables insulation were conducted. To do so, experiment investigations such as mechanical tests, contact angle measurement and water absorption quantification were used to evaluate the impact of UV and thermal aging on the insulating material properties. In order to highlight the structural changes induced by the constraints, a complementary technique, namely FTIR spectroscopy, was monitored. Results show that UV and thermal aging causes significant evolutions in the XLPE properties.
机译:交联聚乙烯(XLPE)电力电缆因其出色的机械和电气性能而越来越多地用于配电系统中。然而,众所周知,在环境条件下的降解是使用这种材料作为电缆绝缘的主要问题。在本文中,对用作高压电力电缆绝缘层的XLPE进行了人工风化试验。为此,使用了诸如机械测试,接触角测量和吸水量化等实验研究来评估紫外线和热老化对绝缘材料性能的影响。为了突出由约束引起的结构变化,监测了一种补充技术,即FTIR光谱。结果表明,紫外线和热老化会导致XLPE性能发生重大变化。