The icing phenomena occurred in south China has seriously affected the safe and stable operation of the power grid. Some research results in this field has been reported in China and some other countries. However, there are rare results related to the parallel flash gap insulator ground icing network. This paper used the finite element analysis software to simulate the parallel gap distance icing flashover voltage, conducted icing tests to the RCSE 100C-2 insulator in artificial climate laboratory, and quantitative analyzed the impact of the parallel gap distance icing flashover voltage. The results show that flashover voltage shunt size and the gap size were intimately related after the icing bridge is formed up between the ground insulators. The flashover voltage was higher when the gap in parallel was larger, and the dry flashover voltage is higher than the wet flashover voltage in the same gap conditions.
机译:华南地区发生的结冰现象严重影响了电网的安全稳定运行。中国和其他一些国家已经报道了该领域的一些研究成果。但是,与并联毛边间隙绝缘子接地结冰网络相关的结果很少。本文使用有限元分析软件模拟了平行间隙距离结冰闪络电压,在人工气候实验室对RCSE 100C-2绝缘子进行了结冰测试,并定量分析了平行间隙距离结冰闪络电压的影响。结果表明,在接地绝缘体之间形成结冰桥之后,闪络电压的分流尺寸和间隙尺寸密切相关。当平行间隙较大时,闪络电压较高,在相同间隙条件下,干闪络电压高于湿闪络电压。