For a 550kV HGIS electromagnetic voltage transformer(PT), ferromagnetic resonance occured after the disconnector was opened. In this paper, firstly, considering the ferromagnetic resonance condition, the fault disintegration, fault recording, and operating overvoltage datas were analyzed to analyze the causes of ferromagnetic resonance.Then a HGIS simulation model was built by EMTP-ATP to calculate very fast transient voltage which was caused by opening operation of disconnector. According to the results, the VFTO amplitude at the PT is not large, but the wave front steepness reaches 2837kV/ μs, which is harmful to the inter-turn insulation of the PT primary winding. It may cause partial inter-turn short circuit and then induce core saturation. Finally, the preventive measures of ferromagnetic resonance are proposed.
机译:对于550kV HGIS电磁电压互感器(PT),隔离开关断开后发生铁磁谐振。本文首先考虑了铁磁谐振条件,分析了故障分解,故障记录和运行过电压数据,分析了铁磁谐振的原因,然后通过EMTP-ATP建立了HGIS仿真模型,以计算非常快的瞬态电压。这是由于隔离开关的断开操作引起的。结果表明,PT的VFTO幅值不大,但波前陡度达到2837kV /μs,对PT初级绕组的匝间绝缘有害。这可能会导致部分匝间短路,然后引起铁芯饱和。最后,提出了防止铁磁共振的措施。