首页> 外文会议>Electrical Insulation Conference and Electrical Manufacturing Coil Winding Technology Conference, 2003. Proceedings >Partial discharge weak spots localization in the stator insulation of running turbo generators
【24h】

Partial discharge weak spots localization in the stator insulation of running turbo generators

机译:运行中的涡轮发电机定子绝缘中的局部放电薄弱点定位

获取原文
获取外文期刊封面目录资料

摘要

One of the best symptoms for the presence of defects in the HV insulation system is the detection of partial discharges (PD). Weak spots may be found by evaluating the PD repetition rate over the entire insulation system. If a severe degradation system is active, it will show a much higher PD repetition rate compared to the non-affected part of the insulation system. A method is introduced, which uses the propagation of the pulses through the stator core to localize partial discharges. With the knowledge of the exact spot at which each PD occurs it is possible to determine the PD repetition rate of PD occurrences in the entire stator. Weak spot localization can then be readily identified and localized by their enhanced repetition rate.
机译:高压绝缘系统中存在缺陷的最佳症状之一是检测局部放电(PD)。通过评估整个绝缘系统上的PD重复率,可以发现弱点。如果一个严重的退化系统处于活动状态,则与绝缘系统的未受影响部分相比,它将显示出更高的PD重复率。引入了一种方法,该方法使用脉冲通过定子铁心的传播来定位局部放电。通过了解每个PD发生的确切位置,可以确定整个定子中PD发生的PD重复率。然后,可以通过增强的重复率轻松识别并定位弱点。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号