Components Testing - Effects of Changing Disinfectants and Other Water Quality Parameters on Lead and Copper Release

机译:组件测试-消毒剂和其他水质参数的变化对铅和铜释放的影响

获取原文
获取原文并翻译 | 示例

摘要

New and used meters and stop valves were provided by participating utilities (SeattlernPublic Utilities and DC Water) and tested using local tap water to measure leaching of lead andrncopper upon exposure to changing disinfectants (free chlorine to chloramines and vice versa) andrnother controlled water quality conditions (pH, alkalinity, phosphate). The tests were conductedrnby a “fill, stand, dump, and refill” procedure. Components were tested at the same time, in thernsame facilities, and using the same water quality as pipe loop testing that was conducted as partrnof this research project. Results showed that high lead and copper levels were measured initiallyrnfrom both new and used components, but levels declined rapidly during baseline tap waterrnconditions. In the absence of phosphate, lowering pH and/or switching from chloramines to freernchlorine resulted in higher metals levels. The lowest lead and copper levels were measured whenrnphosphate was present. After an initial period of conditioning, results from components testingrnprovided supporting data consistent with copper alloy pipe loop testing results.
机译:参与的公用事业公司(西雅图公用事业公司和直流水)提供了新的和使用过的仪表和截止阀,并使用当地的自来水进行了测试,以测量暴露于变化的消毒剂(从游离氯到氯胺,反之亦然)和其他受控水质条件下铅和铜的浸出情况。 (pH,碱度,磷酸盐)。通过“填充,放置,倾倒和重新填充”程序进行测试。在相同的设施中同时对组件进行测试,并使用与本研究项目相同的水管环路测试相同的水质。结果表明,最初从新的和使用过的成分中都测出了高铅和铜含量,但是在基线自来水条件下,其含量迅速下降。在不存在磷酸盐的情况下,降低pH值和/或从氯胺转换为游离氯会导致较高的金属含量。当存在磷酸磷酸根时,最低的铅和铜含量被测量。经过最初的调节后,组件测试的结果提供了与铜合金管道回路测试结果一致的支持数据。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号