首页> 外文会议>9th International Conference on Indoor Air Quality and Climate Vol.3, Jun 30-Jul 5, 2002, Monterey, California >SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY
【24h】

SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY

机译:在不同温度和湿度水平下进行实地实验室研究时,病态建筑的症状和表现

获取原文
获取原文并翻译 | 示例

摘要

Thirty female subjects were exposed for 280 minutes to four conditions in balanced order of presentation: to 20℃/40%, 23℃/50%, 26℃/60% RH at10 L/s/p outside air, and to 20℃/40% RH at 3.5 L/s/p. They performed simulated office work throughout each exposure and repeatedly marked a set of visual-analogue scales to indicate their perception of environmental conditions and of the intensity of SBS symptoms at the time. They were repeatedly reminded to adjust their clothing so as to remain in thermal comfort, and succeeded in doing so. Although perceived air quality improved at lower indoor air temperature and humidity and at the higher ventilation rate, this could not be shown to be associated with any effects on task performance. However, subjects reported significantly more intense SBS symptoms associated with decreased productivity, including fatigue, headache and difficulty in thinking clearly, when they were exposed to raised levels of temperature and humidity.
机译:30名女性受试者以平衡的出现顺序分别暴露于四种条件下280分钟:在20 L / s / p的条件下暴露于20℃/ 40%,23℃/ 50%,26℃/ 60%RH,以及暴露于20℃/在3.5 L / s / p下的相对湿度为40%。他们在每次曝光期间进行模拟办公室工作,并反复标记一组视觉模拟量表,以表明他们当时对环境条件和SBS症状强度的感知。多次提醒他们调整衣服,以保持热舒适,并成功地做到了。尽管在较低的室内空气温度和湿度下以及在较高的通风速率下感知的空气质量得到了改善,但这并未显示出对任务绩效的任何影响。但是,当受试者暴露于升高的温度和湿度下时,他们报告的SBS症状与生产力下降相关的症状更加严重,包括疲劳,头痛和难以清晰思考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号