AN INTERVENTION STUDY OF OUTDOOR AIR SUPPLY RATES AND SICK LEAVE AMONG OFFICE WORKERS

机译:办公室工作人员室外空气供应率和病假的干预研究

获取原文
获取原文并翻译 | 示例

摘要

We conducted an intervention study of outdoor air supply rates and sick leave among hourly office workers employed by Polaroid Corporation. High and moderately high outdoor air supply rates were specified in a random block design in two office buildings. Indoor CO_2 concentrations were measured every ten minutes. We calculated a CO_2 concentration differential by subtracting the daily average CO_2 concentration in the study area during 1-3 AM, when the building was not occupied, from the same-day average concentration between 9-5 PM. The mean weekly, workday, CO_2 concentration differential ranged from 37 to 250 ppm as compared with the ASHRAE recommended maximum differential of 700 ppm. We determined the frequency of sick leave among 294 hourly workers scheduled to work 49804.2 days in the study areas using company records. Generalized additive mixed models showed no association of CO_2 differential at the relatively low values studied and sick leave in the studied buildings.
机译:我们对Polaroid公司雇用的每小时上班族进行了室外空气供应率和病假的干预研究。在两栋办公楼中,以随机区组设计指定了较高和中等较高的室外空气供应率。每隔10分钟测量一次室内的CO_2浓度。我们通过从晚上9点至下午5点之间的当天平均浓度减去研究区中无人居住的研究区在上午1-3点之间的每日平均CO_2浓度,计算出CO_2浓度差。与ASHRAE建议的最大差异700 ppm相比,每周,工作日的平均CO_2浓度差异范围为37至250 ppm。我们使用公司记录确定了计划在研究区域内安排工作49804.2天的294名小时工的频率。广义添加剂混合模型表明,在相对较低的研究值和病假期间,CO_2的差异与研究建筑物之间没有关联。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号