USEPA Sewer Electro Scan Field Demonstration Revisited

机译:再访美国环保局下水道电子扫描场示范

获取原文
获取原文并翻译 | 示例

摘要

Potential Rain Dependent Infiltration (RDI) flows are a critical parameter for the design andrnprioritization of sewer collection system infiltration mitigation projects. An estimate of RDIrnflows may be obtained from the defect current measured by an electro scan of a pipe. RDI flowrnhas been calculated for the pipes electro scanned during the USEPA sponsored fieldrndemonstration. The field demonstration included CCTV inspection of the pipes. For pipe defectsrnthat are potential sources of RDI, the comparison with CCTV showed that electro scan is highlyrnreliable, identified 2.1 times more defects and that many of the defects missed by CCTV werernpotentially the largest sources of infiltration. The distribution of the electro scan estimated RDIrnflow was significantly more variable than that shown by CCTV. This reveals the potential use ofrnelectro scan to target and design rehabilitation projects that will significantly reduce RDI atrnconsiderably lower cost.
机译:潜在的降雨相关渗透(RDI)流量是下水道收集系统渗透缓解项目的设计和优先排序的关键参数。 RDIrnflow的估计值可以从通过管道的电子扫描测量的缺陷电流中获得。已为在USEPA赞助的现场演示中进行电子扫描的管道计算了RDI流量。现场演示包括CCTV管道检查。对于可能是RDI来源的管道缺陷,与CCTV的比较表明,电扫描可靠性高,发现的缺陷多2.1倍,而CCTV遗漏的许多缺陷可能是最大的渗透源。电扫描估计的RDIrnflow的分布比CCTV所示的多得多。这揭示了使用电扫描来瞄准和设计修复项目的潜在用途,这将显着降低RDI并显着降低成本。