首页> 外文会议>2019 5th International Conference on Engineering, Applied Sciences and Technology >Application of Duval Pentagon Compared with Other DGA Interpretation Techniques: Case Studies for Actual Transformer Inspections Including Experience from Power Plants in Thailand
【24h】

Application of Duval Pentagon Compared with Other DGA Interpretation Techniques: Case Studies for Actual Transformer Inspections Including Experience from Power Plants in Thailand

机译:五角大楼与其他DGA解释技术相比的应用:实际变压器检查的案例研究,包括泰国发电厂的经验

获取原文
获取原文并翻译 | 示例

摘要

The interpretation of dissolved gas analysis (DGA) is one of the most important procedure to identify the incipient fault which may occur in transformers. Various interpretation methods can be used; however, they may identify different fault types for the same investigation case. This paper aims to study the performance of DGA interpretation, i.e., IEC Ratio, Duval Triangle and Duval Pentagon, and Doernenburg Ratio. The performance of the DGA interpretation techniques is evaluated from twenty-four fault cases obtained from both academic references and problem investigated transformers utilized in an electrical power plant in Thailand. It was found that the Duval Pentagon method provided the highest consistency DGA interpretation compared with other methods. Duval Pentagon also has the capability to distinguish the normal aging of the insulation system from other fault types.
机译:溶解气体分析(DGA)的解释是识别变压器中可能出现的初期故障的最重要过程之一。可以使用各种解释方法。但是,他们可能会为同一调查案例确定不同的故障类型。本文旨在研究DGA解释的性能,即IEC比率,Duval三角形和Duval五角大楼以及Doernenburg比率。 DGA解释技术的性能是从24个故障案例中进行评估的,这些案例从学术参考文献和泰国发电厂使用的问题变压器中获得。发现与其他方法相比,Duval五角大楼方法提供了最高的一致性DGA解释。杜瓦尔五角大楼还具有将绝缘系统的正常老化与其他故障类型区分开的能力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号