An Analysis on Failure of Circuit Breaker's Closing Resistors in Guiyang 500kV Substation

机译:贵阳500kV变电站断路器合闸电阻失效分析。

获取原文
获取原文并翻译 | 示例

摘要

3-phase closing resistors on 2 500kV circuit breakers in Guiyang substation failed during a short time out of phase operation and caused a big accident. This paper describes the system situation, breaker conditions, field records of the failure and EMTP reproducing results. It is shown from the analysis, besides the grading capacitors' failure, the aging dielectric between resistor contacts that makes its withstand level decreased might be an essential factor which caused the accident. Some comments on the use of closing resistors are concluded.
机译:贵阳变电站的2 500kV断路器上的三相闭合电阻在短时异相运行中发生故障,并造成了大事故。本文介绍了系统状况,断路器状况,故障现场记录和EMTP再现结果。从分析中可以看出,除了分级电容器的故障外,使电阻承受能力降低的电阻触点之间的电介质老化可能是造成事故的重要因素。总结了有关使用闭合电阻器的一些意见。