首页> 外文OA文献 >Arm balancing control and experimental validation of a grid connected MMC with pulsed DC load
【2h】

Arm balancing control and experimental validation of a grid connected MMC with pulsed DC load

机译:具有脉冲直流负载的MMC并网的臂平衡控制和实验验证

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

This paper focuses on the operation of a grid connected Modular Multilevel Converter (MMC) supplying a pulsed DC load. The goal is to achieve minimum AC power fluctuation despite the high power fluctuation present on the DC side. The MMC has been selected for its inherent ability to decouple AC and DC current controllers. How¬ever, if no additional provisions are taken, the pulsed load causes imbalance of cell capacitor voltages between upper and lower arm in each phase. The paper presents the the-oretical analysis of the imbalance problem, and proposes a simple arm balancing controller to enable the operation of the converter under pulsed DC load. The effectiveness of the controller has been successfully verified on a 7 kW MMC experimental prototype with a 3 kA pulsed DC load.
机译:本文着重于提供脉冲直流负载的并网模块化多电平转换器(MMC)的操作。尽管直流侧存在高功率波动,但目标是实现最小的交流功率波动。选择MMC的原因是其具有将交流和直流电流控制器去耦的固有能力。但是,如果不采取其他措施,则脉冲负载会导致每个相位上臂和下臂之间的单元电容器电压不平衡。本文对不平衡问题进行了理论分析,并提出了一种简单的臂平衡控制器,以使转换器能够在脉冲直流负载下工作。该控制器的有效性已经在具有3 kA脉冲直流负载的7 kW MMC实验原型上成功验证。