首页> 美国政府科技报告 >Interruption of a Dry-Type Transformer in No-Load by a Vacuum Circuit-Breaker
【24h】

Interruption of a Dry-Type Transformer in No-Load by a Vacuum Circuit-Breaker

机译:用真空断路器中断空载干式变压器

获取原文

摘要

Overvoltages generated during interruption of a dry type delta-star connected transformer in no load by a vacuum breaker were studied. During interruption of inrush current 37% of the phase-to-ground overvoltages were 5 pu, and 6% 7 pu. Comparison of experimental and theoretical results using Boyle's model shows no discrepancy for inrush currents and clean overvoltages from the steady-state interruption. Overvoltages due to repetitive reignitions (not covered by Boyle's model) are higher than the calculated values during steady-state switching.