首页> 外文期刊>International journal of exergy >Mathematical modelling and performance analysis of a novel auto-cascade refrigeration cycle for ultra-low temperature applications
【24h】

Mathematical modelling and performance analysis of a novel auto-cascade refrigeration cycle for ultra-low temperature applications

机译:

获取原文
获取原文并翻译 | 示例
           

摘要

The main objective of this study is to assess both energetically and exergetically the performance of a novel auto-cascade refrigeration (NACR) cycle enhanced by an internal heat exchanger using R290/R170. In contrast to the ACR cycle with a -60°C evaporation temperature, the NACR cycle displays a COP increase of 140.78 and a 148.67 improvement in exergy efficiency. Additionally, there is a notable decrease of 13.77 in compressor discharge temperature. For an evaporation temperature of -55°C, the NACR cycle achieves a COP of 0.403 and an exergy efficiency of 14.61, with the compressor discharge temperature registering at 126.60°C.

著录项

相似文献

  • 外文文献
  • 中文文献
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有