首页> 外文期刊>Tunnelling and underground space technology >Enhancement of carbon monoxide removal in an underground car park using ventilation system with single and twin jet fans
【24h】

Enhancement of carbon monoxide removal in an underground car park using ventilation system with single and twin jet fans

机译:使用带有单喷和双喷风扇的通风系统,提高地下停车场的一氧化碳去除率

获取原文
获取原文并翻译 | 示例
           

摘要

This study aims to explore many case scenarios of both single and twin jet fans installation in existing ventilation system such as the operation mode, tilt angle and gap distance of the Jet fans on the ventilation efficiency in an underground car park using computational fluid dynamics technique. It was found that the averaged carbon monoxide concentration was 28 ppm after the simulation time of 15 min for conventional ventilation case without jet fans. The inclined single jet fan had lower carbon monoxide concentration than conventional ventilation case. It was found that the straight twin jet fan could remove carbon monoxide gas better than the inclined one. The increasing gap distance increased the carbon monoxide ventilation efficiency of the system. In addition, the energy consumption was analyzed. The inclined single jet fan was potential jet fan installation when considering on both the ventilation efficiency and energy utilization aspects.
机译:这项研究旨在利用计算流体力学技术探索在现有通风系统中安装单排和双排喷气式风扇的许多案例,例如操作模式,喷气式风扇的倾斜角度和间隙距离对地下停车场通风效率的影响。发现在没有喷气风扇的常规通风情况下,经过15分钟的模拟时间后,平均一氧化碳浓度为28 ppm。倾斜的单喷嘴风扇的一氧化碳浓度低于常规通风情况。结果发现,直式双射流风机比倾斜式双射流风机能更好地去除一氧化碳气体。间隙距离的增加增加了系统的一氧化碳通风效率。此外,还分析了能耗。从通风效率和能源利用两个方面考虑,倾斜的单喷嘴风扇是潜在的喷嘴风扇安装。