首页> 外文期刊>IEEE Transactions on Power Delivery >Experimental evaluation of EMTP-based current transformer models for protective relay transient study
【24h】

Experimental evaluation of EMTP-based current transformer models for protective relay transient study

机译:基于EMTP的电流互感器模型用于继电保护暂态研究的实验评估

获取原文
获取原文并翻译 | 示例
           

摘要

This paper describes an EPRI study of current transformer (CT) digital models intended for protective relay transient performance analysis. Experimental evaluation of CT models implemented using the Electromagnetic Transient Program (EMTP) was carried out. Two relaying CTs with 600/5 and 2000/5 ratios were used in the study. Experiments in a high power laboratory were performed to obtain transient responses. Simulation of the CT response to the same transient events was set up using three different CT models. They were implemented based on the saturable transformer and nonlinear reactor models available in an EMTP. Comparison of laboratory and simulation results indicates that CT models developed based on the EMTP program give satisfactory results for most of the cases. It has also been discovered that in some instances EMTP models need further improvements.
机译:本文介绍了旨在保护继电保护暂态性能分析的电流互感器(CT)数字模型的EPRI研究。对使用电磁暂态程序(EMTP)实施的CT模型进行了实验评估。在研究中使用了两个具有600/5和2000/5比率的中继CT。在高功率实验室中进行实验以获得瞬态响应。使用三个不同的CT模型建立了对相同瞬态事件的CT响应的仿真。它们是基于EMTP中可用的饱和变压器和非线性电抗器模型实现的。实验室结果和模拟结果的比较表明,基于EMTP程序开发的CT模型在大多数情况下均提供令人满意的结果。还发现在某些情况下,EMTP模型需要进一步改进。