Adsorption chiller technology is one of the effective means to convert waste thermal energy into effective cooling, which substantially improves energy efficiency and lowers environmental pollution. This paper uses an improved lump-parameter design model to theoretically and experimentally evaluate the efficacy of the passive heat recovery scheme as applied to a four-bed adsorption chiller. Results show that the model can accurately track the experimental temporal system outlet temperatures. The performance predictions from this model compare favourably with experimental results. At rated temperature conditions and over a wide range of cycle times, both the cooling capacity and COP can be predicted to within 12.5%. The analyses indicate that the model can be used confidently as a design tool for a four-bed adsorption chiller and the passive heat recovery scheme can effectively improve the system performance.
机译:吸附式冷却器技术是将废热能转化为有效冷却的有效手段之一,可大大提高能源效率并减少环境污染。本文使用改进的集总参数设计模型从理论上和实验上评估了应用于四床吸附式制冷机的被动式热回收方案的有效性。结果表明,该模型可以准确跟踪实验时间系统出口温度。该模型的性能预测与实验结果相比具有优势。在额定温度条件下和宽范围的循环时间范围内,预计制冷量和COP均在12.5%以内。分析表明,该模型可以放心地用作四床吸附式冷却器的设计工具,而被动式热回收方案可以有效地改善系统性能。

著录项

  • 来源
    《Mathematical Problems in Engineering》 |2015年第14期|634347.1-634347.10|共10页
  • 作者单位

    Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China.;

    Univ Tasmania, ICT, Hobart, Tas 7001, Australia.;

    Univ Western Australia, Sch Mech & Chem Engn, Crawley, WA 6009, Australia.;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号