首页> 外文期刊>電気学会論文誌. B >Study of DC Withstand Test as After-Laying Test for 500kV XLPE Cable
【24h】

Study of DC Withstand Test as After-Laying Test for 500kV XLPE Cable

机译:500kV XLPE电缆的直流耐压试验作为后置试验的研究

获取原文
获取原文并翻译 | 示例
           

摘要

To evaluate the suitability of the DC withstand test for use as the after-laying test for extrahigh-voltage XLPE cable lines, especially 500-kV XLPE cable lines, we studied the effectiveness of the DC withstand test and the influence of DC voltage application on AC insulating performance, using XLPE cables with artificial defects. DC breakdown strength of the cable with defects does not decrease radically compared with AC breakdown strength due to space charge effects.
机译:为了评估直流耐压测试作为超高压XLPE电缆线路(尤其是500 kV XLPE线缆)的后置测试的适用性,我们研究了直流耐压测试的有效性以及直流电压施加对使用具有人工缺陷的XLPE电缆,具有交流绝缘性能。由于空间电荷的影响,具有缺陷的电缆的直流击穿强度与交流击穿强度相比不会显着降低。