...
首页> 外文期刊>IEEE Power Electronics Letters >PWM methods to handle time delay in digital control of a UPS inverter
【24h】

PWM methods to handle time delay in digital control of a UPS inverter

机译:用于处理UPS逆变器数字控制中的时间延迟的PWM方法

获取原文
获取原文并翻译 | 示例
           

摘要

With the popularity of micro-processors, digital controllers are widely used in uninterruptible power supply (UPS) inverters. These digital control systems of UPS inverters require a time interval for sampling and computation, which sometimes affects the performance of inverters. In this paper, the problem of time delay in digital control of a UPS inverter is discussed. Then two novel pulsewidth modulation (PWM) methods, the two-polarity PWM method and the asymmetric PWM method, are proposed to handle the time-delay problem. Both of these PWM methods can achieve a wide range of duty ratio between 0.05-0.95, which is independent of inverter model. Furthermore, they are easy to implement using a digital micro-controller. Experimental results are presented in the paper to verify feasibility of the proposed PWM methods.
机译:随着微处理器的普及,数字控制器已广泛用于不间断电源(UPS)逆变器中。这些UPS逆变器的数字控制系统需要一定的时间间隔进行采样和计算,这有时会影响逆变器的性能。本文讨论了UPS逆变器数字控制中的时延问题。然后提出了两种新颖的脉宽调制(PWM)方法,即两极性PWM方法和非对称PWM方法,以解决时延问题。这两种PWM方法均可实现0.05-0.95的宽占空比,这与逆变器模型无关。此外,它们很容易使用数字微控制器来实现。本文给出了实验结果,以验证所提出的PWM方法的可行性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号