首页> 外文期刊>Fire Safety Journal >Multi-point opacity measurement in a fire environment using a network of optical fibres
【24h】

Multi-point opacity measurement in a fire environment using a network of optical fibres

机译:使用光纤网络在火灾环境中进行多点不透明度测量

获取原文
获取原文并翻译 | 示例
           

摘要

Opacity measurements were carried out in a smoke layer using a light source and photodiodes located outside the hot environment, using a network of optical fibers to transport the incident and attenuated light. The whole system was designed with protections for the emission and reception points against smoke, droplets and water vapor generated by a water mist system. It was tested first in laboratory conditions in order to assess its stability at high temperature or in a water spray. Its accuracy regarding the transmission measurement "was then evaluated using a reference material. It was used after these qualifications steps in a fire smoke layer flowing along a corridor ceiling, in order to provide a stratification profile based on transmittance data. Results were compared to the stratification data obtained with classical thermocouple measurements. The analysis showed similar conclusions without spray: the vertical evolution in temperature and transmission indicated a similar smoke-free layer, around 1.20 m high in the 2.40 m high corridor when smoke was produced by a 250 kW heptane pool fire in a neighboring room. When studying smoke/mist interactions using a nozzle injecting water in the corridor, a perfect mixing was deduced from temperature measurements, while some discrepancies still appeared with the opacimeters, indicating some variations in the particle concentrations. The opacity could serve to predict these concentration profiles and the visibility in the smoke/droplet medium. (C) 2016 Elsevier Ltd. All rights reserved.
机译:使用光源和位于热环境外的光电二极管在烟层中进行不透明度测量,并使用光纤网络传输入射光和衰减光。整个系统设计有针对发射和接收点的保护装置,以防止水雾系统产生的烟雾,水滴和水蒸气。首先在实验室条件下对其进行了测试,以评估其在高温或喷水条件下的稳定性。然后使用参考材料评估其关于透射测量的准确性。在经过这些鉴定步骤之后,将其用于沿着走廊天花板流动的火烟层中,以便根据透射率数据提供分层曲线。将结果与通过经典热电偶测量获得的分层数据分析结果表明,不使用喷雾,得出的结论相似:温度和透射率的垂直演变表明类似的无烟层,当250 kW庚烷产生烟雾时,在2.40 m高的走廊中约高1.20 m。在走廊上注水时,当研究烟雾/烟雾的相互作用时,从温度测量值可以得出完美的混合效果,而浊度仪仍会出现一些差异,表明颗粒浓度存在某些差异。可以用来预测这些浓度曲线和烟雾/液滴介质。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

  • 来源
    《Fire Safety Journal》 |2016年第7期|7-14|共8页
  • 作者单位

    Univ Lorraine, CNRS, LEMTA, 2 Ave Foret Haye,TSA 60604, F-54518 Vandoeuvre Les Nancy, France;

    Univ Lorraine, CNRS, LEMTA, 2 Ave Foret Haye,TSA 60604, F-54518 Vandoeuvre Les Nancy, France|CSTB, 84 Ave Jean Jaures, F-77447 Marne La Vallee 2, France;

    CSTB, 84 Ave Jean Jaures, F-77447 Marne La Vallee 2, France;

    CSTB, 84 Ave Jean Jaures, F-77447 Marne La Vallee 2, France;

    Univ Lorraine, CNRS, LEMTA, 2 Ave Foret Haye,TSA 60604, F-54518 Vandoeuvre Les Nancy, France;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Opacity; Transmission; Visibility; Smoke; Water spray; Stratification;

    机译:不透明;透射;能见度;烟;喷水;分层;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号