Tap changers have not changed radically since their invention in the early part of this century. They are slow in operation, typically traversing 19 taps in around 100 seconds, and require frequent maintenance. Previous attempts to devise improved tap changers have concentrated upon thyristor assisted or all solid-state units. For various reasons none of these schemes has been adopted. A new GTO thyristor assisted tap changer is introduced here which addresses the problems of previous schemes. It eliminates excessive conduction losses which are inherent in solid-state tap changers, and at the same time provides a fast response speed by means of fast acting vacuum switches. Calculations show that it will be possible to traverse a 19 tap range in around 0.5 s. A unit for a 240 MVA transformer will require minimal maintenance as the vacuum switches used in the selector and diverter never make or break more than a few amperes. Test results are given for a 3 kVA transformer and tap changer unit.
机译:自从本世纪初发明以来,分接开关并没有发生根本的变化。它们的运行速度很慢,通常会在100秒左右的时间内移动19个水龙头,并且需要经常维护。以前设计改进的分接开关的尝试集中在晶闸管辅助或所有固态单元上。由于各种原因,没有采用这些方案。这里介绍了一种新的GTO晶闸管辅助分接开关,它解决了先前方案的问题。它消除了固态分接开关固有的过大传导损耗,同时通过快速作用的真空开关提供了快速的响应速度。计算表明,有可能在大约0.5 s的时间内遍历19个抽头范围。用于240 MVA变压器的单元将需要最少的维护,因为选择器和分流器中使用的真空开关永远不会超过或超过几安培。给出了3 kVA变压器和分接开关单元的测试结果。