摘要

This paper presents an approach for alleviation of network over loads in the day-to-day operation of power systems under deregulated environment. The control used for over load alleviation is real power generation rescheduling based on relative electrical distance (RED) concept. The method estimates the relative location of load nodes with respect to the generator nodes. The contribution of each generator for a particular over loaded line is first identified, then based on RED concept the desired proportions of generations for the desired overload relieving is obtained, so that the system will have minimum transmission losses and more stability margins with respect to voltage profiles, bus angles and better transmission tariff. Results obtained for network overload alleviation of suitably modified IEEE 39-bus New England system are presented for illustration purposes.
机译:本文提出了一种缓解管制环境下电力系统日常运行中网络过载的方法。用于减轻过载的控制是基于相对电气距离(RED)概念的实际发电调度。该方法估计负载节点相对于生成器节点的相对位置。首先确定每个发电机对特定过载线路的贡献,然后基于RED概念,获得用于所需过载消除的所需发电比例,从而使系统具有最小的传输损耗和相对于电压的更大稳定性裕量外形,母线角度和更好的传输价格。出于说明目的,介绍了通过适当修改的IEEE 39总线新英格兰系统缓解网络过载所获得的结果。