首页> 外文期刊>Electric power systems research >Voltage control with on-load tap changers in medium voltage feeders in presence of distributed generation
【24h】

Voltage control with on-load tap changers in medium voltage feeders in presence of distributed generation

机译:存在分布式发电时,在中压馈线中使用有载分接开关进行电压控制

获取原文
获取原文并翻译 | 示例
           

摘要

This paper discusses voltage regulation on medium-voltage feeders with distributed generation (DG) using on-load tap changer (LTC) and line drop compensation (LDC). The analysis shows that LTC is robust against DG, whereas DG can affect the effectiveness of the voltage regulation provided by LDC. However, with proper coordination between DG and LDC, it is possible to ensure voltage regulation without unnecessarily restricting the integration of DG. It is shown that, while lowering the LTC setting can increase the DG integration limit, even higher increase can be obtained by activating the LDC feature, which is present in most LTCs, but often not used. LDC regulation is also compared with other alternatives such as using a DG unit with voltage control capability and installing a line voltage regulator.
机译:本文讨论了使用有载分接开关(LTC)和线路压降补偿(LDC)的分布式发电(DG)的中压馈线的电压调节。分析表明,LTC对DG具有鲁棒性,而DG可影响LDC提供的电压调节的有效性。但是,通过DG和LDC之间的适当协调,可以确保电压调节而不会不必要地限制DG的集成。结果表明,虽然降低LTC设置可以增加DG积分限制,但通过激活LDC功能(即使在大多数LTC中都存在但通常不使用),可以获得更高的增加。还可以将LDC调节与其他替代方案进行比较,例如使用具有电压控制功能的DG单元和安装线路电压调节器。