Analytical prediction of abnormal temporary overvoltages due to ground faults in MV networks

机译:中压电网接地故障引起的异常临时过电压的分析预测

获取原文
获取原文并翻译 | 示例
           

摘要

The paper deals with the temporary overvoltages that build up in radial MV distribution networks following the inception of a 1-phase-to-ground fault. It will be demonstrated that, for extended cable/overhead MV distribution networks with ungrounded neutral, in case of low resistance faults at critical locations along overhead lines, the neutral voltage can reach very large values, significantly higher than 1 p.u. (up to 2.5 p.u.). The attendant temporary overvoltages on healthy phases can be very large, much higher than √3 p.u. (up to 3.5 p.u.). Fault currents are also affected, reaching twice the value calculated with simplified methods, i.e. neglecting series impedances. Quick yet accurate analytical formulas for the prediction of maximum overvoltages, fault currents and critical fault distances are presented, together with their validation by detailed ATP-EMTP simulations. The results of a study on an existing Italian 15 kV-50 Hz extended mixed cable/overhead distribution network are finally presented and discussed.
机译:本文讨论了从1相接地故障开始后径向MV配电网络中累积的临时过电压。将证明,对于中性点未接地的扩展电缆/架空MV配电网络,在架空线路关键位置的低电阻故障情况下,中性点电压可以达到非常大的值,大大高于1p.u。 (最多2.5 p.u.)。健康阶段的随之而来的临时过电压可能非常大,远高于√3p.u。 (最大3.5 p.u.)。故障电流也会受到影响,达到简化方法计算值的两倍,即忽略串联阻抗。给出了用于预测最大过电压,故障电流和关键故障距离的快速而准确的分析公式,并通过详细的ATP-EMTP仿真对其进行了验证。最后介绍并讨论了对现有的意大利15 kV-50 Hz扩展混合电缆/架空配电网络的研究结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号