首页> 外文期刊>Electric power systems research >A WAMS/PMU-based fault location technique
【24h】

A WAMS/PMU-based fault location technique

机译:基于WAMS / PMU的故障定位技术

获取原文
获取原文并翻译 | 示例
           

摘要

A WAMS (wide-area measurement/monitoring system)/PMU (phasor measurement unit)-based fault location technique is proposed in this paper. The technique uses synchronized fault voltages of two nodes of the faulted line and their neighboring nodes for fault location. Based on these fault node voltages measured by PMUs, line currents between these nodes can be calculated. Then, node injection currents at two terminals of the faulted line are formed from the line currents. Based on the calculated fault node injection currents, fault node can be deduced or fault location in transmission lines can be calculated accurately. Fault location formulas are derived in full details. Case studies on IEEE-14-bus system and a testing network with 500 kV transmission lines including ATP/EMTP simulations are given to validate the proposed technique. Various fault types and fault resistances are also considered.
机译:本文提出了一种基于WAMS(广域测量/监视系统)/ PMU(相量测量单元)的故障定位技术。该技术将故障线路的两个节点及其相邻节点的同步故障电压用于故障定位。基于由PMU测量的这些故障节点电压,可以计算这些节点之间的线路电流。然后,由线路电流形成故障线路两端的节点注入电流。基于计算出的故障节点注入电流,可以推导出故障节点,或者可以准确地计算出传输线中的故障位置。故障定位公式的详细信息。通过对IEEE-14总线系统和500 kV传输线的测试网络(包括ATP / EMTP模拟)进行案例研究,以验证所提出的技术。还考虑了各种故障类型和故障电阻。