首页> 外文会议>International Conference on Engineering Research and Development >Performance Indicators for Sapele Thermal Power Station, Nigeria: 1997-2006
【24h】

Performance Indicators for Sapele Thermal Power Station, Nigeria: 1997-2006

机译:尼日利亚SAPELE热力电站的性能指标:1997-2006

获取原文

摘要

Performance indices as measured by percentage of shortfall of energy generated, load factor, utilization factor and capacity factor of Sapele thermal power station, Nigeria in the period 1997 to 2006 is presented. The thermal station uses both steam and gas turbines. The station consists of six units of steam turbine and four units of gas turbine with total installed capacity of 1020 MW. But it was established that less than 17% of the installed capacity was available. The percentage shortfall of energy generated for the period under review ranged from 27.4 to 49.1%. This was due to aging of the plant, improper operation and maintenance. The load factor was between 39.9 and 64% as against international best practice of 80%. The inability of Power Holding Company of Nigeria (PHCN) to do turn-around maintenance on the plant was advanced for the dismal value. Average plant availability of the plant for the studied period was less than 21% as against Industry best practice of over 95%. The capacity factor was even more dismal. For the period under review, it ranged from as low as 5.49% in 2006 to the highest value of 17.19% in 1997. Low capacity factor indicates excessive plant failure. Measures to improve the performance indices of the plant have been suggested such as training of operation and maintenance (O & M) personnel regularly, improvement in O & M practices, proper spare parts inventory, organizing regular management meetings and improving general housekeeping of the plant.
机译:提出了尼日利亚的能源产生,负荷因子,利用率因数,尼日利亚的能量产生,负荷因数,利用因子和容量系数测量的性能指标。热站使用蒸汽和燃气轮机。该站由六个单位的蒸汽轮机和四个燃气轮机组成,总装机容量为1020 MW。但建立了不到17%的装机容量。该审查期间所产生的能量缺少的百分比范围为27.4至49.1%。这是由于植物老化,操作不当和维护。负载因子在80%的国际最佳实践中达到39.9至64%。为令人沮丧的价值提出了尼日利亚(PHCN)的电力控股公司的无能为力,为工厂进行转弯维护。植物的平均植物可用于学习期的可用性小于21%以上的行业最佳实践超过95%。容量因素甚至更令人沮丧。在审查期间,2006年的低至5.49%至1997年的最高值为17.19%。低容量因素表明植物失效过高。提出了改进工厂性能指标的措施,例如经营和维护(O&M)人员定期培训,改善O&M实践,适当的备件库存,组织定期管理会议,改善植物的一般管家。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号