Fast Fault Restoration Control Scheme for LCC AC Side Fault for Hybrid HVDC Transmission Systems Using Flexible DC Voltage Control

机译:混合直流输电系统采用柔性直流电压控制的LCC交流侧故障快速故障恢复控制方案

获取原文

摘要

Hybrid HVDC transmission systems, which consist of a line commutated converter (LCC) operating in rectifier mode and a voltage source converter (VSC) operating in inverter mode, have a number of advantages: improve inverter immunity against commutation failure, reduced converter cost & semiconductor losses, and enhanced reactive power support capability. However, due to the slower operating speed of LCC, the recovery process after AC fault clearance requires significant time. To improve the recovery speed, this paper proposes a control scheme under which the VSC inverter perceives the LCC-side fault state by its measured instantaneous DC current and coordinate its DC voltage operation. A detailed model of a Hybrid HVDC transmission system is established in Matlab/Simulink to demonstrate the effectiveness, and the simulation results show the proposed scheme reduces the rectifier's grid fault restoration time of the Hybrid HVDC system operation compared with traditional control schemes.
机译:混合HVDC传输系统,由在整流模式下运行的线路换向转换器(LCC)和以逆变器模式运行的电压源转换器(VSC)组成,具有许多优点:提高变频器免疫防止换向故障,降低转换成本和半导体损失,增强无功功率支持能力。但是,由于LCC的运行速度较慢,交流故障清除后的恢复过程需要很大的时间。为了提高回收速度,本文提出了一种控制方案,在该控制方案下,VSC逆变器通过其测量的瞬时DC电流感知LCC侧故障状态并坐标其直流电压操作。在MATLAB / Simulink中建立了混合HVDC传输系统的详细模型,以证明仿真结果,仿真结果表明,与传统的控制方案相比,建议的方案降低了混合HVDC系统操作的整流器电网故障恢复时间。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号