首页> 外文会议>Power and Energy Engineering Conference (APPEEC), 2010 >Analyse on Relay Maloperation of Assembling Capacitor Bank for Internal Fault Protection
【24h】

Analyse on Relay Maloperation of Assembling Capacitor Bank for Internal Fault Protection

机译:内部故障保护用组合电容器组继电保护误动作分析

获取原文

摘要

In this paper, internal fault protective relay maloperation of assembling capacitor bank caused by switching-on transient harmonics is analyzed. Mathematical expressions describing the adaptive settings of single-wye, dual-wye and bridge connections are given. The realistic action of internal fault protections under high amplitude harmonic conditions is possibly very different from theoretic setting. Major impact of harmonic is to change the maximum allowed fault units in the capacitor banks on which the relay action settings are tight depend. The paper deduces this change under harmonic condition and actual investigation results corroborate the rationality of the research work. Corresponding measure against the relay maloperation is discussed.
机译:本文分析了通过开启瞬态谐波引起的电容器组组装电容器组的内部故障保护继电器。给出了描述单个WYE,双层WYE和桥接连接的自适应设置的数学表达式。在高幅度谐波条件下内部故障保护的现实行为可能与理论设置非常不同。谐波的主要影响是改变继电器动作设置紧密的电容器组中的最大允许故障单元。本文在谐波条件下推出了这种变化,实际调查结果证实了研究工作的合理性。讨论了对继电器恶作剧的相应措施。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号