首页> 外文会议>International Conference on Electrical Machines >Partial Non-Zero Fault Response of Grid-Connected DFIG
【24h】

Partial Non-Zero Fault Response of Grid-Connected DFIG

机译:网格连接DFIG的部分非零故障响应

获取原文

摘要

This paper presents a detailed experimental study of wind turbine DFIG response to non-zero grid faults that may occur at a considerable distance from the generator. An analytical solution of the generalized DFIG machine equations operating under non-zero fault conditions is developed in which the fault response is separated into three components: a natural response that describes zero voltage behavior, a component describing the retained voltage behavior and the forced response corresponding to the applied rotor voltage via the rotor-side power converter. The DFIG system fault response is examined experimentally using a 7.5kW test facility detailing example of a 500ms, 15% fault.
机译:本文介绍了对从发电机相当距离可能发生的非零网格故障的风力涡轮机DFIG响应的详细实验研究。开发了在非零故障条件下运行的广义DFIG机器方程的分析解决方案,其中故障响应分为三个组件:一种描述零电压行为的自然响应,描述了描述保留的电压行为和强制响应的组件通过转子侧功率转换器到施加的转子电压。使用500ms,15%故障的7.5kW测试设施进行实验检查DFIG系统故障响应。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号