摘要

One of the main challenges with HVDC multi-terminal (MTDC) configurations, which are based on voltage source converters (VSC), is the protection system. The dc grids have small series inductances which made them unable to limit the rise time of the DC current when a dc fault occurs. For this reason, the dc fault clearing must be performed very fast in order to limit the effect of the rapid increase of the dc current during dc faults. However, before clearing the line, the fault must be detected and located as soon as possible. The fault location is very challenging using conventional methods that have been used in ac system. This paper investigates a fault location algorithm based on inverse-time overcurrent characteristic. In this algorithm the protection operating time is inversely changed with the current magnitude, so in order to implement it, feed inductor at each cable terminal is needed. A simplified version of CIGRE B4 DC Grid Test System is implemented in PSCAD to test the proposed algorithm.
机译:保护系统是基于电压源转换器(VSC)的HVDC多端子(MTDC)配置的主要挑战之一。直流电网的串联电感较小,因此在发生直流故障时无法限制直流电流的上升时间。因此,必须非常快速地执行直流故障清除,以限制直流故障期间直流电流快速增加的影响。但是,在清除线路之前,必须尽快检测并定位故障。使用已经在交流系统中使用的常规方法,故障定位非常具有挑战性。本文研究了一种基于反时限过电流特性的故障定位算法。在该算法中,保护工作时间与电流大小成反比,因此,为了实现该保护工作,需要在每个电缆端子处馈入电感。在PSCAD中实现了CIGRE B4直流电网测试系统的简化版本,以测试所提出的算法。