Lightning seriously endanger safety operation of oil rig. The transient behaviour of oil derrick subjected to a lightning strike is investigated using the field theory approach. An oil derrick connected to two different grounding systems is studied. The lightning strike is simulated by injecting a 30kA current surge having a double exponential. Two different lightning strike scenarios are examined: (i) oil derrick with natural grounding system, (ii) oil derrick with manual grounding system. The results show that oil derrick with manual grounding system just has a little lower scalar potentials and step voltages. The reason is that the number of vertical ground rods of manual grounding system is too small and depth of burying is too shallow.
机译:雷电严重危害石油钻机的安全运行。使用场论方法研究了井架遭受雷击的瞬态行为。研究了连接到两个不同接地系统的井架。通过注入具有双指数的30kA电流浪涌来模拟雷击。研究了两种不同的雷击场景:(i)具有自然接地系统的井架,(ii)具有手动接地系统的井架。结果表明,带有手动接地系统的井架仅具有较低的标量电势和阶跃电压。原因是手动接地系统的垂直接地棒数量太少,埋深太浅。