Experimental study of transients and electrical fields caused by lightning flashover in the uhvdc converter station

机译:特高压直流换流站雷击引起的瞬变和电场的实验研究

获取原文
获取原文并翻译 | 示例

摘要

When lightning strikes the DC transmission line and causes flashover, the transients propagating in the primary circuit and impulse electromagnetic field generated in the station might cause interference or even block fault of the UHVDC system. In this paper, artificial short-circuit (DC line to ground) experiments are conducted out on an operating ± 800 kV DC system at different distances to the converter station, to simulate the lightning fault process, meanwhile the transient voltages and currents as well as the electrical fields are measured by advanced sensors and high sampling rate devices at different points in the converter station. It's the first time that such experiments are carried out on a ± 800 kV DC system, with a comprehensively study of both the circuit and filed lightning transient characteristics.
机译:当雷电击中直流输电线路并引起闪络时,在一次回路中传播的瞬变和站点中产生的脉冲电磁场​​可能会引起UHVDC系统的干扰甚至阻塞故障。本文在距变电站不同距离的±800 kV直流系统上进行了人工短路(直流线接地)实验,以模拟雷电故障过程,同时模拟瞬态电压和电流以及电场由先进的传感器和高采样率设备在换流站的不同位置进行测量。这是首次在±800 kV直流系统上进行此类实验,并全面研究了电路和现场雷电瞬态特性。